Raised Access Flooring
What is Raised Access Flooring
A Raised Access Flooring provides an elevated structural floor above a solid substrate (often a concrete slab) to create a hidden void for the passage of mechanical and electrical services. Raised floors are widely used in modern office buildings, and in specialized areas such as command centers, IT data centers and computer rooms, where there is a requirement to route mechanical services and cables, wiring, and electrical supply. Such flooring can be installed at varying heights from 2 inches (51 mm) to heights above 4 feet (1,200 mm) to suit services that may be accommodated beneath. Additional structural support and lighting are often provided when a floor is raised enough for a person to crawl or even walk beneath.
In the U.S., underfloor air distribution is becoming a more common way to cool a building by using the void below the raised floor as a plenum chamber to distribute conditioned air, which has been done in Europe since the 1970s.In data centers, isolated air-conditioning zones are often associated with raised floors. Perforated tiles are traditionally placed beneath computer systems to direct conditioned air directly to them. In turn, the computing equipment is often designed to draw cooling air from below and exhaust into the room. An air conditioning unit then draws air from the room, cools it, and forces it beneath the raised floor, completing the cycle.
Design
The panels are normally made of steel-clad particleboard or a steel panel with a cementitious internal core, although some tiles have hollow cores. Panels may be covered with a variety of flooring finishes to suit the application, such as carpet tiles, high-pressure laminates, marble, stone, and antistatic finishes for use in computer rooms and laboratories. When using a panel with a cement top surface the panels are sometimes left bare and sealed or stained and sealed to create a tile appearance and save the customer money. This bare application is used most often in office area, hallways, lobbies, museums, casinos, etc.
Many modern computer and equipment rooms employ an underfloor air distribution to ensure even cooling of the room with minimal wasted energy. Conditioned air is provided under the floor and dispersed upward into the room through regularly spaced diffuser tiles, blowers or through ducts directed into specific equipment. Automatic fire protection shutoffs may be required for underfloor ventilation, and additional suppression systems may be installed in case of underfloor fires.
Many office buildings now use access flooring to create more flexible and sustainable spaces. When underfloor air is designed into a building from the start of the project, the building can be less expensive to build and less expensive to operate over the life of the building. Underfloor air requires less space per floor, thereby reducing the overall height of the building, which in turn reduces the cost of the building facade. The blowers and air handlers required for underfloor air are much smaller and require less energy, since hot air rises naturally through the space as it comes in contact with people and equipment that warm the air and it rises to the ceiling. Additionally, when buildings are designed to combine modular electrical, modular walls, and access floor, the space within the building can be reconfigured in a few hours, as compared to historical means of demolishing walls and drilling holes in the floor to route electrical and other services.
Because the flooring tiles are rarely removed once equipment has been installed, the space below them is seldom cleaned, and fluff and other debris settles, making working on cabling underneath the flooring a dirty job. Smoke detectors under the raised floor can be triggered by workers disturbing the dust, resulting in false alarms.
Cooling load implications
The installation of a raised floor system can change the thermal behavior of the building by reducing the interaction between the heat gains and the thermally massive concrete slab. The raised floor serves as a separation between the room and the slab. Energy simulations of an office building located in San Francisco showed that the mere presence of the raised floor affects the zone cooling load profile and tends to increase the peak cooling load. When carpeting is present the negative impact of the raised floor on zone peak cooling load may be reduced.
Telecommunications data center applications
Raised floors available for general purpose use typically do not address the special requirements needed for telecommunications applications.
The general types of raised floors in telecommunications data centers include: stringerless, stringered, and structural platforms; and, truss assemblies.
- Stringerless raised floors – an array of pedestals that provide the necessary height for routing cables and also serve to support each corner of the floor panels.
- Stringered raised floors – a vertical array of steel pedestal assemblies (steel base plate, tubular upright, and a head) uniformly spaced on 2-foot centers and mechanically fastened to the concrete floor.
- Structural platforms – members constructed of steel angles or channels that are welded or bolted together to form an integrated platform for supporting equipment.
- Truss assemblies – utilizing attachment points to the sub floor to support a truss network on which the floor panels rest. The truss has high lateral strength and transfers lateral loads to the sub floor with less strain than possible with a vertical pedestal assembly.
A telecommunications facility may contain continuous lineups of equipment cabinets. The most densely populated installation configuration would consist of rows of continuous 2-foot-wide equipment cabinets with aisles that separate 2-foot-wide adjacent rows. This lineup configuration is considered to be the most densely populated in terms of square foot area and, therefore, the largest floor load anticipated for a raised floor system. Considering prorated aisle space, a single equipment cabinet will then occupy an 8-square foot (0.74-m2) floor area (4 square feet for the cabinet and 4 square feet of aisle).
The data center can be located in remote locations, and is subject to physical and electrical stresses from sources such as fires and from electrical faults.
The environment drives the installation methods for raised floors, including site preparation, cable and cable racking, bonding and grounding, and fire resistance. The actual installation should be in accordance with the customer’s practices.